2. Advanced Power Management
Intelligent PDU Web Interface
PDU Tab > Status > Device
Item Definition
HOST/GUEST#
Select the role of PDU (HOST or GUEST#) if PDUs are daisy
chained. Up to 3 GUEST PDUs can connect to 1 HOST PDU.
Load
Device Load
Load current of the connected device(s), measured in Amps.
Load power of the connected device(s), measured in Kilowatts
and Kilovolt-Amps.
Bank Load* Load current of the bank, measured in Amps.
Power Factor Power factor of the connected device(s).
Peak Load
Maximum load current recorded and the time of occurrence.
Users can reset the value to zero at Power Restore in
PDU Ta b
> Manager > Device
.
Energy
Total energy consumed by the connected device(s) from the
reset date, measured in kWh.
Users can reset the value to zero at Power Restore in
PDU Ta b
> Manager > Device
.
Utility
Voltage Voltage of the utility power.
Frequency Frequency of the utility power.
*Only available in select models.