EasyManua.ls Logo

Daiichi Electronics SQLC-110L - Page 6

Daiichi Electronics SQLC-110L
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SQLC-214-097
5
② Current input
Setting item 3-phase 3-wire Single-phase 3-wire Single-phase
1 Display combination
Pattern Pattern 15 Pattern 15 Pattern 15
Main monitor A(V) A(U) A
Sub-monitor (Left) A(U) A(W)
Sub-monitor (Center) A(W) A(N)
Sub-monitor (Right)
Bar graph A(V) A(U) A
2
Alarm
output
(
)
Alarm 1
Factor DA DA DA
Reset form AUTO AUTO AUTO
Contact delay time 0 second 0 second 0 second
Test
Alarm 2
Factor DA DA DA
Reset form AUTO AUTO AUTO
Contact delay time 0 second 0 second 0 second
Test
3
Demand
detection
Demand
current
Upper limit value 80.0A 400A 40.0A
Interval 0 second 0 second 0 second
4
Harmonic
detection
Current
Distortion-factor upper limit OFF OFF OFF
5th conversion content rate upper
limit
OFF OFF OFF
n-th content rate
Factor 5th 5th 5th
Upper limit OFF OFF OFF
5th conversion detection characteristics
Inverse-time-delay
mode
Inverse-time-delay
mode
Inverse-time-delay
mode
Average value time limit 0 minute 0 minute 0 minute
5
Leakage detection
(
)
Rated sensitivity current 0.1A 0.1A 0.1A
Factor switching Io Io Io
Circuit switching 1 phase earthing 1 phase earthing 1 phase earthing
Use ZCT selection Type 0 Type 0 Type 0
6 Backlight
Action AUTO AUTO AUTO
Brightness 3(Middle) 3(Middle) 3(Middle)
7 Measurement range
Current range 100.0A 500A 50.0A
Current display peculiar
sensitivity
100.0A 500A 50.0A
8
Analog output
(
)
Output factor 1 A(V) A(U) A
Output factor 2 A(U) A(W)
Output factor 3 A(W) A(N)
Output factor 4
Output peculiar
sensitivity
Current 100.0% 100.0% 100.0%
Low input cut OFF OFF OFF
9
External operation
input (
)
Input 1 function Alarm reset Alarm reset Alarm reset
Input 2 function Max./Min. reset Max./Min. reset Max./Min. reset
10
Measurement display
ON/OFF
Current ON ON ON
Harmonic current ON ON ON
Current leakage (
) ON ON ON
11 Input circuit Phase line change (
) 3φ3W 1φ3W (U-N-W) 1φ2W
12 Measurement
Dead band 0.0% 0.0% 0.0%
Tidal current measurement General measurement General measurement General measurement
13 Analog output specification (
)(
) 1‐5V 1‐5V 1‐5V
14
Analog output
adjustment
(
)
Output 1
Bias adjustment 0.0% 0.0% 0.0%
Span adjustment 100.0% 100.0% 100.0%
Output 2
Bias adjustment 0.0% 0.0% 0.0%
Span adjustment 100.0% 100.0% 100.0%
Output 3
Bias adjustment 0.0% 0.0% 0.0%
Span adjustment 100.0% 100.0% 100.0%
Output 4
Bias adjustment 0.0% 0.0% 0.0%
Span adjustment 100.0% 100.0% 100.0%
Note(
) A setting item is not displayed in case there is no corresponding option.
The external operation input constitutes default value with an alarm-output option.
It becomes the next function in case there is no alarm-output option.
Input 1 function:Max. / Min. reset, Input 2 function:Measurement factor change.
Note(
) A setting item is not displayed if analog output is except DC0-5V (or DC1-5V) specification,
And analog output insulation product does not display a setting item.
Note(
) When the setting of phase line change of an input circuit is changed, it will return to the default value
of phase line which all set value changed.

Related product manuals