1 Troubleshooting
Service manual
27
EBLQ+EDLQ011~016CAV3+W1 + EBLQ+EDLQ011~016CA3V3+W1
+ EK(2)CB07CAV3 + EKMBUHCA3V3+9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
Root cause category: component – mechanical
Possible failure Root cause Check Repair
Limited heat exchange between
refrigerant loop and heat sink
inverter could result in high inverter
temperatures and limited
compressor frequency.
Bad contact between refrigerant
loop and inverter heat sink,
Lack of refrigerant.
Check contact between refrigerant
loop and inverter PCB heat sink.
Root cause category: component – electrical
Possible failure Root cause Check Repair
Discharge pipe thermistor – higher
temperature measured than actual.
Deviation of thermistor (higher
temperature measured than
actual).
Check discharge pipe thermistor. Replace discharge pipe thermistor
or main PCB.
Heat sink inverter thermistor -
deviation.
Deviation of thermistor (higher
temperature measured than
actual).
Check heat sink inverter
thermistor,
Check inverter PCB.
Replace heat sink inverter
thermistor,
Replace inverter PCB.
Expansion valve incorrect control -
superheat too high.
Faulty suction thermistor,
Faulty expansion valve control.
Check suction thermistor,
Check the expansion valve.
Replace suction thermistor,
Replace expansion valve.
Increased compressor sound level
Root cause category: component – mechanical
Possible failure Root cause Check Repair
Compressor increased bearing
friction/bearing failure.
Bad lubrication of compressor
internal rotating parts,
Compressor at end of lifetime.
No checks possible. Replace compressor.
Unit produces (loud) noise or
shakes.
Refrigerant overcharge,
Mixing of air in refrigerant
system,
Refrigerant undercharge.
Check refrigerant. After vacuum drying, charge
correct amount of refrigerant.
Root cause category: component – electrical
Possible failure Root cause Check Repair
Expansion valve incorrect control -
superheat too low.
Faulty suction thermistor,
Faulty expansion valve control.
Check suction thermistor,
Check the expansion valve.
Replace thermistor when
required,
Replace expansion valve when
required.
1.5.8 Abnormal presence of ice
Possible failure Root cause Check Repair
General ice build-up. Outdoor unit installation MUST be
protected from weather (wind,
snow, ...).
See installer reference guide for
correct installation.
Ice build-up on the outdoor unit. Clogged drain holes,
Snow on the outdoor unit,
Ice building up on the casing.
Ice is NOT in direct contact with
fins.
Unclog drain holes or remove
any scraps that can be used for
ice to build up,
Remove ice.
Defrost operation malfunction. NOT enough defrost power:
shortage of refrigerant.
Check refrigerant charge,
Check for leaks.
Replace refrigerant,
Fix leaks.
Ice build-up at entry spot of
refrigerant.
Refrigerant shortage. Check refrigerant charge,
Check for leaks.
Replace refrigerant,
Fix leaks.