SiUS281811EA Centralized Control Group No. Setting
Part 3 Remote Controller 97
5.2 Wireless Remote Controller
Group No. setting by wireless remote controller for centralized control
1. When in the normal mode, press INSPECTION/TEST button for 4 seconds or more to enter field
setting mode.
2. Set mode No. 00 with MODE button.
3. Set the group No. for each group with UP button or DOWN button.
4. Enter the selected group numbers by pressing RESERVE button.
5. Press INSPECTION/TEST button and return to the normal mode
UP button
DOWN button
MODE button
RESERVE button
Mode No.
Field setting mode
Group No.
INSPECTION/TEST
button