Field Settings from Outdoor Unit SiUS281811EA
170 Part 5 Field Settings and Test Operation
2.2 Setting Mode and Monitor Mode
The following 3 modes can be changed over with the button switches on the PCB and you can find
the present mode by the status of the H1P indicator.
(1) Setting mode 1 (H1P OFF)
Initial status (normal) : Also indicates during abnormal.
(2) Setting mode 2 (H1P ON)
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
(3) Monitor mode (H1P blinks)
Used to check the program made in setting mode 2.
H1P H3P H5P H7P
H2P H4P H6P
BS1
(MODE)
BS2
(SET)
BS4
(TEST)
BS5
(RESET)
BS3
(RETURN)
Contents display
Monitor mode
Press the RETURN (BS3) button.
Press the RETURN (BS3) button.
Setting mode 2
Press the RETURN (BS3) button.
Press the RETURN (BS3) button.
Press the RETURN (BS3) button.
Press the MODE (BS1) button.Press the MODE (BS1) button.
Press the MODE (BS1) button.
Select a setting condition
with the
SET (BS2) button
.
Select a setting item with
the SET (BS2) button.
Select a check item with
the SET (BS2) button.
Setting condition
(Contents) display
Setting mode 1
(Initial condition)
MODE
OFF
H1P
Press the MODE (BS1) button for more
than 5 seconds.
MODE
ON
H1P
H1P
Blinking
MODE

Table of Contents