Outline of Control (Indoor Unit) SiUS281811EA
124 Part 4 Functions and Control
Note(s)
6. Outline of Control (Indoor Unit)
6.1 Remote Controller Thermistor
Temperature is controlled by both the remote controller thermistor and suction air thermistor (1)
for the indoor unit. (This is however limited to when the field setting for the remote controller
thermistor is set to Use.)
When fresh air intake kit is used, outdoor air is mixed with indoor air, and the room temperature
may not reach the set temperature, since TS and TH1 do not enter the area in which remote
controller thermistor can be used. In such case, install the remote sensor (optional accessory) in
your room, and set the field settings to not use the remote controller thermistor.
FTQ-TA models do not have this control because they do not have suction air thermistor. The
thermistor is selectable manually when remote sensor (optional accessory) is installed.
Cooling If there is a significant difference in the set temperature and the suction temperature, fine
adjustment control is carried out using a suction air thermistor (1), or using the remote controller
thermistor near the position of the user when the suction temperature is near the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 30°C (86°F) (A F):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat is off.)
Suction air thermistor (1) is used for temperatures from 18°C (64°F) to 23°C (73°F) (A C).
Remote controller thermistor is used for temperatures from 23°C (73°F) to 27°C (81°F) (C E).
Set temperature
(Ts)
32
30
28
26
24
22
20
18
16
(°C)
(°C)
TH1 = Ts – 1
TH1 = Ts + 1
TH1 = Ts + 3
TH1 = Ts – 3
A B C D E F
12 14 16 18 20 22 24 26 28 30 32 34
Range in which remote controller
thermistor can be used
Range in which
suction air thermistor
can be used
Suction temperature (TH1)
Differential
(°F)
(°F)
90
86
82
79
75
72
68
64
60
54 57 60 64 68 72 75 79 82 86 90 93