EasyManua.ls Logo

Daikin SkyAir FHQ24PVJU - Fan Motor Connector Check

Daikin SkyAir FHQ24PVJU
331 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check SiUS281811EA
306 Part 6 Service Diagnosis
5.13 Fan Motor Connector Check
CHECK 16 FCQ-TA, FAQ-TA
Resistance measuring points and judgment criteria.
FHQ-P, FHQ-M
Resistance measuring points and judgment criteria.
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
FG
Vsp
Vcc
GND
Vdc
X20A
Measuring points Judgment criteria
1 - 4
1 Ω
2 - 4
3 - 4
7 - 4
1 Red
2 White
3 Black
X4A
Measuring points Judgment criteria
1 - 3 53.5 ± 10%
2 - 3 31.6 ± 10%

Table of Contents

Other manuals for Daikin SkyAir FHQ24PVJU

Related product manuals