Troubleshooting by Error Codes SiUS281811EA
228 Part 6 Service Diagnosis
4.11 Indoor Fan Motor Status Abnormality
Error Code A6-20
Applicable
Models
FTQ-TA
Outline The indoor unit periodically receives control status information from the fan motor.
Error is issued when the information shows abnormality.
Error Decision
Conditions
If the information shows Power Limit or Temp Limit status, it will be deemed a MOTOR LIMIT
abnormal operation. (The system can keep operating.)
If the information shows Motor Lost Control or Current Trip status, it will be deemed a MOTOR
TRIP abnormal operation. (The system stops operating.)
Error Reset
Conditions
If the indoor unit stops receiving abnormal information, the error will be cleared.
Supposed
Causes
Fan or motor obstruction
Blocked filters
Power interruption (low voltage)
Incorrect wiring
Blockage in the airflow (ductwork) or ductwork undersized
High loading conditions
Corrective
Actions
Check for obstruction on the fan, motor, or ductwork.
Clean filters.
Check filters, grille, duct system, heat exchanger air inlet/outlet for blockages.
Verify the input voltage at the motor.
Check wiring.
Replace motor.
CHECK 19 Refer to page 311.