SiUS281811EA Field Settings from Outdoor Unit
Part 5 Field Settings and Test Operation 185
2.11 Setting of Heat Pump Lockout and Emergency Heat Mode
Heat pump is locked out when the setting below and/or external input to ABC terminal has been
made.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
16
Setting of
heat pump
lockout 1
khkhhhh
OFF
khhhhhk
ON
khhhhkh
37
Setting of
heat pump
lockout 2
kkhhkhk
OFF
khhhhhh
Mode 1
khhhhhk
Mode 2
khhhhkh
Mode 3
khhhhkk
Mode 4
khhhkhh
Mode 5
khhhkhk
Mode 6
khhhkkh
Type Description
Actions
Field setting
Shorted
between
Heating Thermo-on Heating Thermo-off
Heater Fan Heater Fan
I–
Heat-pump heating is
always locked out
2-16: ON ON ON (H/L) OFF LL
II
Mode 1
Lockout is controlled
by ABC terminals
2-37: Mode 1
A-C
ON
ON (H/L)
OFF
LL
FFOC-B
Mode 2 (for a heater
which does not need
airflow)
2-37: Mode 2
LLLLC-A
B-C OFF OFF
Mode 3 Lockout is controlled
by the outdoor air
temperature and
setpoint which is
configured by the field
setting 2-57 and 2-47
2-37: Mode 3 Same as 2-37: Mode 1, A-C shorted
detrohs C-B ,1 edoM :73-2 sa emaS4 edoM :73-24 edoM
detr
ohs C-A ,2 edoM :73-2 sa emaS5 edoM :73-25 edoM
detrohs C-B ,2 edoM :73-2 sa emaS6 edoM :73-26 edoM