EasyManua.ls Logo

Daikin SkyAir FHQ24PVJU - Power Transistor Check

Daikin SkyAir FHQ24PVJU
331 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiUS281811EA Check
Part 6 Service Diagnosis 295
5.4 Power Transistor Check
CHECK 4 Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
[Point of Measurement and Judgment Criteria]
· Measure the resistance value using a tester at each point of measurement below, 10 minutes later
after power OFF.
To use analog multimeter:
Measurement in the resistance value mode in the range of multiplying 1 kΩ.
To use digital multimeter:
Measurement is executed in the diode check mode.( )
[Preparation]
· Multimeter
Preparing a multimeter in the analog system is
recommended.
A multimeter in the digital system with diode check
function will be usable.
No.
Point of
Measurement
Judgment
Criteria
Remarks
+–
1P2 U
2 ~ 15 kΩ 2P2 V
3P2 W
4U P2
15 kΩ and
above
(including
)
Due to condenser
charge and so on,
resistance
measurement may
require some time.
5V P2
6W P2
7N3 U
8N3 V
9N3 W
10 U N3
2 ~ 15 kΩ 11 V N3
12 W N3
No.
Point of
Measurement
Judgment
Criteria
Remarks
+–
1P2 U
1.2 V and
over
Due to condenser
charge and so on,
resistance
measurement may
require some time.
2P2 V
3P2 W
4U P2
0.3 ~ 0.7 V
5V P2
6W P2
7N3 U
8N3 V
9N3 W
10 U N3
1.2 V and
over
Due to condenser
charge and so on,
resistance
measurement may
require some time.
11 V N3
12 W N3

Table of Contents