SiUS281811EA Protection Control
Part 4 Functions and Control 121
4.4 Inverter Protection Control
Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an error, or transient inverter overcurrent, and radiation fin temperature increase.
Tfin: Radiation fin temperature
Inverter overcurrent protection control
Inverter radiation fin temperature control
Not limited
Limited
Inverter current > 22 A
Inverter current > 22 A
Inverter current 22 A × 10% continues for 260 seconds
Inverter current 22 A
Compressor upper limit: Maximum frequency
&
10 seconds
Matching of frequency
&
Compressor upper limit
frequency: 1-step down from
current compressor frequency
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Inverter current
standby
Inverter current 22 A
continues for 3 minutes
Current step maintained
Without conditions
When occurring 4 times within 60 minutes,
the error code
L8
is output.
Not limited
Limited
Tfin t79°C (174.2°F)
Tfin t79°C (174.2°F)
Tfin t84°C (183.2°F)
Fin temperature standby
Tfin < 76°C (168.8°F)
Compressor upper limit: Maximum frequency
&
Compressor upper limit
frequency: 1-step down from
current compressor frequency
10 seconds
Matching of frequency
&
Tfin d76°C (168.8°F)
continues for 3
minutes
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Current step maintained
Without conditions
When occurring 4 times within 60
minutes
,
the error code
L4
is output.