EasyManua.ls Logo

Daikin SkyAir FHQ24PVJU - Electronic Expansion Valve Coil Check

Daikin SkyAir FHQ24PVJU
331 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check SiUS281811EA
308 Part 6 Service Diagnosis
5.14 Electronic Expansion Valve Coil Check
CHECK 18 Measure the connector pin-to-pin resistance and make sure that the resistance value is within the
range listed in the table below.
FCQ-TA, FTQ-TA
FBQ-P, FAQ-TA
Orange 1
Red 2
Yellow 3
Black 4
— 5
Gray 6
Measuring points Judgment criteria
1 - 6
35-55 Ω
2 - 6
3 - 6
4 - 6
White 1
Yellow 2
Orange 3
Blue 4
Red 5
Brown 6
Measuring points Judgment criteria
1 - 3 300 Ω
1 - 5 150 Ω
2 - 4 300 Ω
2 - 6 150 Ω

Table of Contents

Other manuals for Daikin SkyAir FHQ24PVJU

Related product manuals