Troubleshooting by Error Codes SiUS281811EA
230 Part 6 Service Diagnosis
4.13 Swing Flap Motor Abnormality
Error Code A7
Applicable
Models
FHQ-P, FHQ-M
Method of Error
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Error Decision
Conditions
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing flap
motor is energized for a specified amount of time (about 30 seconds).
Error code is displayed but the system operates continuously.
Supposed
Causes
Defective swing motor
Defective connection cable (power supply and limit switch)
Defective micro-switch
Defective indoor unit main PCB