SiUS281811EA Troubleshooting by Error Codes
Part 6 Service Diagnosis 231
Note(s)
Troubleshooting
1. Connector and indoor unit PCB
Connect correctly.
Is the
connector (1)
correctly connected?
NO
YES
Connect correctly.
Is
the limit
switch's connector
(2) correctly
connected?
NO
Replace the indoor unit PCB.
Replace the indoor unit PCB.
208-230 VAC?
NO
YES
Does the
swing flap motor swing?
Does
continuity/no continuity
reverse?
NO
NO
Turn the power supply OFF
once and back ON, and check
whether the swing flap motor
swings when the power
supply is turned back ON.
Turn the power supply OFF
once and restart, and measure
the output voltage of connector
(3) when the power supply is
restarted.
Disconnect the connector
(2), turn the power supply
OFF once and restart, and
check if the limit switch has
continuity when the power
supply is restarted.
YES
YES
Replace the swing flap motor.
YES
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Model
Connector for swing flap motor
PCB
1 2 3
FHQ X6A, X9A X9A X6A A1P