SiUS281811EA Field Setting from Remote Controller
Part 5 Field Settings and Test Operation 149
1.4 List of Field Settings for Indoor Unit
: Factory setting
Mode
No.
(2)
First
Code
No.
Description
Second Code No.
Page
Reference
01 02 03 04
10 (20)
0
Filter
cleaning
sign interval
Ultra long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
153
Long life filter Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard filter Approx.
200
hrs.
Approx.
100 hrs.
0 (8) Filter sign setting Light
Heavy 153
1Filter type Long life filter
Ultra long life filter 153
1 (8) Filter cleaning sign interval Short interval
Long interval 153
2
Remote controller thermistor Remote
controller
thermistor +
Suction air
thermistor
Only suction air
thermistor
Only remote
controller
thermistor
153
2 (8)
Remote sensor and remote
controller thermistor
Only remote
sensor thermistor
Only remote
controller
thermistor
153
3 Filter cleaning sign Displayed
Not displayed 155
6
Remote controller thermistor
control during group control
Not permitted
Permitted 153
7 (6)
Time for absence area
detection
30 minutes
60 minutes 155
11 (21)
1 (8)
Auxiliary electric heater ON
temperature: Ton
Refer to the page on the right for details. 1561
Auxiliary electric heater
ON/OFF temperature: Ton/Toff
2 (8)
Auxiliary electric heater OFF
temperature: Toff
3
Setting of airflow rate when
heating
Standard
Slightly increased Increased 156
3 (8) Electric heater setting Refer to the page on the right for details. 157
5 (8) Electric heater capacity setting Refer to the page on the right for details. 157
6 (6)
Setting the rate of human
detection
High sensitivity Low sensitivity
Standard
sensitivity
Infrared
presence
sensor
disabled
157
7
Automatic airflow adjustment
OFF
Completion of
airflow adjustment
Start of
airflow
adjustment
158
8 (6)
Compensating the temperature
around people
Suction air
temperature only
Priority given on
the suction air
temperature
Standard
Priority given
on the floor
temperature
159
9 (6)
Compensating the floor
temperature when heating
–4°C (–7.2°F) –2°C (–3.6°F) 0°C (0°F)
2°C (3.6°F) 159