Field Setting from Remote Controller SiUS281811EA
156 Part 5 Field Settings and Test Operation
Note(s)
1.5.5 Auxiliary Electric Heater ON/OFF Temperature
1. S value varies automatically based on the room temperature trend.
There is a limitation of combination between Ton and Toff as below due to 2°C (3.6°F) hysteresis
required for reliability.
h: Available
—: Not available
1.5.6 Setting of Airflow Rate when Heating
The fan revolution is changed to maintain the sufficient distance for warm air to reach during the
heating operation. The setting should be changed depending on the installation condition of the
unit.
: Factory setting
Note that this setting is effective only during the heating operation.
Set temperature
Toff + S(1)
Ton + S (1)
Thermostat
OFF
Thermostat
ON
FCQ-TA : Factory setting
Mode No.
First Code
No.
Symbol
Second Code No.
01
02 03 04 05 06
11 (21) 1
Ton
-4°C
(-7.2°F)
3.5°C
(6.3°F)
3°C
(5.4°F)
2.5°C
(4.5°F)
2°C
(3.6°F)
1.5°C
(2.7°F)
Toff
-2°C
(-3.6°F)
1.5°C
(2.7°F)
1°C
(1.8°F)
0.5°C
(0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
FTQ-TA : Factory setting
Mode No.
First Code
No.
Symbol
Second Code No.
01
02 03 04 05 06
11 (21)
1Ton
-4°C
(-7.2°F)
3.5°C
(6.3°F)
3°C
(5.4°F)
2.5°C
(4.5°F)
2°C
(3.6°F)
1.5°C
(2.7°F)
2Toff
-2°C
(-3.6°F)
1.5°C
(2.7°F)
1°C
(1.8°F)
0.5°C
(0.9°F)
0°C
(0°F)
0.5°C
(0.9°F)
Second Code No.
Ton
01 02 03 04 05 06
4°C
(7.2°F)
3.5°C
(6.3°F)
3°C
(5.4°F)
2.5°C
(4.5°F)
2°C
(3.6°F)
1.5°C
(2.7°F)
Toff
06 0.5°C (0.9°F) hhhhhh
05 0°C (0°F) hhhhh
04 0.5°C (0.9°F) hhhh——
03 1°C (1.8°F) hhh———
02 1.5°C (2.7°F) hh————
01 2°C (3.6°F) h —————
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21) 3
01
Standard
02 Slightly increased
03 Increased