SiUS281811EA Troubleshooting by Error Codes
Part 6 Service Diagnosis 257
4.31 Inverter Compressor Motor Lock
Error Code E5
Applicable
Models
All outdoor units
Method of Error
Detection
PCB takes the position signal from UVW line connected between the inverter and compressor, and
the error is detected when any abnormality is observed in the phase-current waveform.
Error Decision
Conditions
This error will be output when the inverter compressor motor does not start up even in forced
startup mode.
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5 MPa (72.5 psi) and above)
Incorrect UVW wiring
Defective PCB
Stop valve is not opened
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the stop valve open?
Check the compressor cable
for disconnection and flaws.
NO
The compressor cable
has a defect.
YES
YES
Are wire
connections made to
phases U, V, and W in the
proper order and
manner?
NO
YES
NO
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Onsite causes.
Open the stop valve.
Replace the cable, and
then securely connect the
connectors.
Make wire connections
without a mistake.
Power OFF
U
V
W
A
Connect correctly.
NO
YES
Does wire follow the
wiring diagram?
Go to the next page.