SiUS281811EA Outline of Control (Indoor Unit)
Part 4 Functions and Control 139
Note(s)
&
&
OR
Condition A
Heater ON permission (Defrost/oil return): 1 (4)
&
Condition B
Condition C
No fan motor system error
High pressure condition: ON (1)
Liquid pipe temperature condition: ON (2)
Heater ON permission (Defrost/oil Return): 0 (4)
Not during defrost/oil return
No fan motor system error
During defrost/oil return
Heater ON permission (Defrost/oil return): 1 (∗4)
OR
Not during defrost/oil return
Fan motor system error
Heater ON permission (Defrost/oil return): 0 (∗4)
1: High pressure condition
2: Liquid pipe temperature condition
3: Auxiliary heater enabled
4: Heater ON permission (Defrost/oil return)
5: Field setting 11 (21)-5. Refer to page 157.
6: Refer to page 157.
ON
OFF
49
120.2
54
129.2
Tc
(˚C)
(˚F)
ON
OFF
46
114.8
49
120.2
TH2
(˚C)
(˚F)
1:
&
Electric heater setting (Field setting 11 (21)-3): 2, 4, 6, 8, 10, 12 (6)
Electric heater capacity setting 01
0: Other than the above
1: Electric heater setting (Field setting 11 (21)-3): 8, 10, 12 (6)
0: Electric heater setting (Field setting 11 (21)-3): 2, 4, 6 (6)