Loading...
SiUS281811EA Field Settings from Outdoor Unit
Part 5 Field Settings and Test Operation 181
: ON : OFF l : Blink
)3()2()1(
Setting
No.
Setting
contents
itteSnoitacidni .oN gnitteS ng No. indication Setting
contents
Setting contents indication (Initial setting)
H1PH2PH3PH4PH5PH6PH7PH1PH2PH3PH4PH5PH6PH7P H1PH2PH3PH4PH5PH6PH7P
12 External
low noise /
demand
setting
NO
(Factory
setting)
l
YES
l
22 Night-time
low noise
setting
OFF
(Factory
setting)
Level 1
l
Level 2
l
Level 3
l l
26 Night-time
low noise
operation
start setting
8:00 PM
l
10:00 PM
(Factory
setting)
l
12:00 AM
l
27 Night-time
low noise
operation
end setting
6:00 AM
l
7:00 AM
l
8:00 AM
(Factory
setting)
l
29 Capacity
precedence
setting
Low noise
precedence
(Factory
setting)
l
Capacity
precedence
l
30 Demand
setting 1
60 % of
rated power
consumption
l
70 % of
rated power
consumption
(Factory
setting)
l
80 % of
rated power
consumption
l
32 Constant
demand
setting
OFF
(Factory
setting)
l
ON
l
Setting mode indication section Setting No. indication section Set contents indication section