1 | Troubleshooting
Service manual
11
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
1.5.6 C9-00 – Room thermistor abnormality
Trigger Effect Reset
Resistance value is out of
range. Temperature
measured <–43.6°C or
>90°C.
Unit will stop operating. Automatic reset when
resistance is within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the room thermistor. See "2.18Thermistors"[4119].
Possible cause: Faulty room thermistor.
2 Perform a check of the indoor unit PCB. See "2.8Indoor unit PCB"[471].
Possible cause: Faulty indoor unit PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.7 CC-00 – Humidity sensor abnormality
Trigger Effect Reset
Disconnected sensor
Broken sensor
Communication error
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the humidity sensor. See "2.6Humidity sensor"[466].
Possible cause: Faulty humidity sensor.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.8 CE-00 – Intelligent thermal sensor abnormality
Trigger Effect Reset
Disconnected sensor
Broken sensor
Communication error
Unit will stop operating. Manual reset via user
interface.