EasyManua.ls Logo

Daikin Stylish Series - F3-00 - Outdoor Unit: Malfunction of Discharge Pipe Temperature; F6-00 - Outdoor Unit: Abnormal High Pressure in Cooling

Daikin Stylish Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 | Troubleshooting
Service manual
18
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
1.5.16 F3-00 – Outdoor unit: Malfunction of discharge pipe temperature
Trigger Effect Reset
Discharge pipe thermistor
detects a too high
temperature.
Unit will NOT stop
operating.
Automatic reset when
temperature drops
normal level.
If the error re-occurs too
soon: unit will stop
operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check that all stop valves of the refrigerant circuit are open. See
"3.2Refrigerant circuit"[4133].
Possible cause: Closed stop valve in the refrigerant circuit.
2 Check if the refrigerant circuit is correctly charged. See "3.2 Refrigerant
circuit"[4133].
Possible cause: Refrigerant overcharge.
3 Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See "3.2Refrigerant circuit"[4133].
Possible cause: Non‑condensables and/or humidity in the refrigerant circuit.
4 Check if the refrigerant circuit is clogged. See "3.2Refrigerant circuit"[4133].
Possible cause: Clogged refrigerant circuit.
5 Perform a check of the 4‑way valve. See "2.14-way valve"[439].
Possible cause: Faulty 4‑way valve.
6 Perform a check of the expansion valve. See "2.3Expansion valve"[454].
Possible cause: Faulty expansion valve.
7 Perform a check of the main PCB. See "2.11Main PCB"[481].
Possible cause: Faulty main PCB.
8 Perform a check of all refrigerant side thermistors. See
"2.18Thermistors"[4119].
Possible cause: Faulty refrigerant side thermistor(s).
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.17 F6-00 – Outdoor unit: Abnormal high pressure in cooling
Trigger Effect Reset
Outdoor heat exchanger
thermistor measures a
too high temperature.
Unit will NOT stop
operating.
Automatic reset when
temperature drops.

Table of Contents

Related product manuals