EasyManua.ls Logo

Daikin Stylish Series - Humidity Sensor; Checking Procedures; Repair Procedures

Daikin Stylish Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 | Components
Service manual
66
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
CAUTION
Overheating the pressure switch will damage or destroy it.
4 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
5 Connect the Faston connectors to the high pressure switch.
6 Add refrigerant to the refrigerant circuit, see "3.2.2 Repair
procedures"[4137].
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
2.6 Humidity sensor
2.6.1 Checking procedures
1 As there is no specific check procedure for this component, first perform a
check of the indoor unit PCB to check if the humidity sensor needs to be
replaced. See "2.8.1Checking procedures"[471].
After complete check of the indoor unit
PCB, is the problem solved?
Action
Yes No further actions required.
No Replace the humidity sensor, see
"2.6.2Repair procedures"[466].
2.6.2 Repair procedures
To remove the humidity sensor
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "2.13Plate work"[499].
1 Disconnect the humidity sensor connector from the indoor unit PCB.
2 Carefully click the complete humidity sensor PCB assembly out of the indoor
unit.

Table of Contents

Related product manuals