2 | Components
Service manual
89
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
Class 20~35
a Fuse
Class 42~50
a Fuse
Is the problem solved? Action
Yes No further actions required.
No Return to "2.11.1Checking
procedures"[481] of the PCB and
continue with the next procedure.
2.12 Outdoor unit fan motor
2.12.1 RXA20~35A3+5 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the propeller fan blade assembly
Prerequisite: Stop the unit operation via the user interface.