2 | Components
Service manual
85
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
Class 42~50
a Fuse
Blown fuse on the main PCB? Action
Yes Replace the blown fuse, see
"2.11.2Repair procedures"[485].
No Return to "2.11.1Checking
procedures"[481] of the main PCB and
continue with the next procedure.
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
2.11.2 Repair procedures
To correct the wiring from the main power supply terminal to the main PCB
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see "2.13Plate work"[499].
2 Make sure that all wires are firmly and correctly connected, see "5.2Wiring
diagram"[4145].
3 Check the continuity of all wires.
4 Replace any damaged or broken wires.
Is the problem solved? Action
Yes No further actions required.
No Return to "2.11.1Checking
procedures"[481] of the PCB and
continue with the next procedure.