EasyManua.ls Logo

Daikin Stylish Series - H9-00 - Outdoor Unit: Malfunction of Outdoor Air Thermistor; J3-00 - Outdoor Unit: Malfunction of Discharge Pipe Thermistor; J6-00 - Outdoor Unit: Malfunction of Heat Exchanger Thermistor

Daikin Stylish Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 | Troubleshooting
Service manual
23
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
1.5.23 H9-00 – Outdoor unit: Malfunction of outdoor air thermistor
Trigger Effect Reset
Outdoor air thermistor
input is out of range.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the outdoor air thermistor. See "2.18Thermistors"[4119].
Possible cause: Faulty ambient air thermistor.
2 Perform a check of the main PCB. See "2.11Main PCB"[481].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.24 J3-00 – Outdoor unit: Malfunction of discharge pipe thermistor
Trigger Effect Reset
Discharge pipe thermistor
input is out of range.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the discharge pipe thermistor. See
"2.18Thermistors"[4119].
Possible cause: Faulty discharge pipe thermistor or connector fault.
2 Perform a check of the main PCB. See "2.11Main PCB"[481].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.25 J6-00 – Outdoor unit: Malfunction of heat exchanger thermistor
Trigger Effect Reset
Outdoor heat exchanger
thermistor input is out of
range.
Unit will stop operating. Manual reset via user
interface.

Table of Contents

Related product manuals