EasyManua.ls Logo

Daikin Stylish Series - Page 138

Daikin Stylish Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 | Third party components
Service manual
138
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
2 Completely open the stop valves by screwing the stop valve screw
counterclockwise.
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
To replace the clogged/leaking part of the refrigerant circuit
1 See the correct procedure for the component that needs to be repaired. See
also "Repair information"[4139] for more details.
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
To recuperate the refrigerant
Prerequisite: Stop the unit operation via the user interface.
1 Manually open all expansion valves.
2 Connect the vacuum pump, manifold, recovery unit, and refrigerant bottle to
the service port of the refrigerant circuit as shown below.
H
V R
L
c
b
a
a Vacuum pump
b Connect flexible hose to service port
c To recovery pump
L Low pressure
H High pressure
V Vacuum
R Refrigerant
3 To add refrigerant, see "3.2.2Repair procedures"[4137].

Table of Contents

Related product manuals