2 | Components
Service manual
53
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
4 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02MPa.
5 Wrap a wet rag around the compressor pipes and solder the compressor pipes
to the refrigerant pipes.
a Compressor pipe
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
6 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
7 Connect the Faston connectors to the compressor wire terminals U, V and W
a Faston connector
8 Install the cover of the compressor wire terminals.