2 | Components
Service manual
57
(C)(F)TXA15~50A(W)(S)(T) + (C)(F)TXA15~50B(B)(S)(T) + RXA42+50A +
RXA20~35A + RXA42+50B
Split Stylish R32
ESIE18-03C – 2020.02
1 If needed, remove any parts or insulation to create more space for the
removal.
2 Pull up the expansion valve motor to remove it from the expansion valve
body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
ab
a Expansion valve motor
b Expansion valve motor harness
INFORMATION
The expansion valve and motor can have a different configuration / layout.
3 Cut all tie straps that fix the expansion valve motor harness.
4 Disconnect the expansion valve motor connector from the main PCB.
5 To install the expansion valve motor, see "2.3.2Repair procedures"[456].
To remove the expansion valve body
Prerequisite: Recuperate the refrigerant from the refrigerant circuit, see
"3.2.2Repair procedures"[4137].
Prerequisite: If needed, remove any parts or insulation to create more space for
the removal.
1 Remove the expansion valve motor, see "2.3.2Repair procedures"[456].
2 Remove the putty. Keep for re-use.

Table of Contents

Related product manuals