EasyManua.ls Logo

Daitsu FMCD*ECM series - Page 27

Daitsu FMCD*ECM series
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 27 of 62
SK2014SON002TechMnlFMCD003
FANMODE
a) Indoorfanrunsatthesetspeedwhileheater,AUX1,AUX2,MTV1andMTV2areturnedoff.
b) Indoorfanspeedcanbeadjustedtolow,mediumandhigh.
HEATMODE
Withoutelectricalheater 
a) MTV1,MTV2,AUX2andheaterarealwaysoff.
b) IfTr≤Ts
‐1ºC(or‐4ºCifeconomycontactisactivated),thenheatoperationisactivatedandAUX1
isturnedon.Indoorfanrunsatthesetspeed.
c) IfTr>Ts,thenheatoperationisterminatedandAUX1isturnedoff.Indoorfanrunsat200rpm.
d) TherangeofTs
is16‐30ºC.
e) Indoorfanspeedcanbeadjustedtolow,medium,highandauto.
Withelectricalheaterasbooster
a) MTV1,MTV2andAUX2arealwaysoff.
b) IfTr≤Ts‐1ºC(or‐4ºCifeconomycontactisactivated),thenheatoperationisactivatedandAUX1
is
turnedon.Indoorfanrunsatthesetspeed.
c) IfTr>Ts,thenheatoperationisterminatedandAUX1isturnedoff.Indoorfanrunsat200rpm.
d) IfTi1<40ºC,thentheelectricalheateristurnedon.If40ºC≤Ti1<45ºC,thentheelectricalheater
maintainsitsoriginalstate.IfTi1≥45ºC,thentheelectricalheateristurnedof f.
e) TherangeofTsis16‐30ºC.
f) Indoorfanspeedcanbeadjustedtolow,medium,highandauto.
PREHEAT
WithoutElectricalHeater
a) MTV1,MTV2andAUX2areoff.
b) If
Ti1 < 36ºC (or > 28ºC is selected by DIPBS2 position SW4), then AUX1 is turned on
whileindoorfanremainsoff.
c) If Ti1≥38ºC (or < 30ºC is selected by DIPBS2 position SW4), then AUX1 is turned on
whileindoorfanrunsatsetspeed.
d) If
the indoor coil temperature sensor is damaged, then the preheat time is set for 2
minutesandtheindoorfanrunsatsetspeed.
WithElectricalHeater
a) Iftheindoorfanspeed≥300RPM,thentheelectricalheaterwillturnon.

Table of Contents

Related product manuals