C.1.12. OperationOfControlPanelOnHigh‐WallUnit
C.1.12.1. On/OffSwitch
a) ThisisatactileswitchtoselectCool→Heat→Offoperaonmode.
b) InCOOLmode,thesettemperatureofthesystemis24ºCwithautofanspeedandswing.Therearenotimer
andsleepmodes.
c) InHEATmode,thesettemperatureofthe
systemis24ºCwithautofanspeedandswing.Therearenotimer
andsleepmodes.
d) Masterunitthatdoesnotuseawallpadwillgloballybroadcast.
Note:Whenbuttonpressingiseffective,themasterunitbuzzerwillbeeptwiceandtheslaveunitwillbeeponce.
C.1.12.2. ElectricHeaterSafetySwitch
a) Before the electrical heater is turned on, the EH safety switch must be closed. If this contact is opened
continuously≥1second,theheaterwill beturnedoff immediatelyandreport anerror.Oncethe contactis
returnedtotheclosedposition≥60seconds,reset
theerrorandthehea terwillstartagain.
b) ShouldtheEHsafetyswitchbeopened≥3timeswithin60minutestheheaterisnotallowedtostartan ymore.
Turnofftheunittoresetthefault,providedthattheswitchhasreturnedtotheclosedposition.