C.2.1. LEDIndicationandErrorDescription
Forallunits‐OperationLEDlight(Green)
ErrorDescription Blink Reason Remedy
Electricalheaterfailure
GreenLEDblinks1times,
stopsfor3s
OnlyforunitwithEH.
EHsafetyswitchis
open.
1. Changefanspeedtohigh.
2. ReplacethedamagedEHsafety
switch.
Indoorcoilsensor2failure
GreenLEDblinks2times,
stopsfor3s
Ti2sensorunpluggedor
damaged.
1. CheckifTi2plugisconnectedornot.
2. Checkifsensor’sresistanceiscorrect
ornot.
Returnairsensorfailure
GreenLEDblinks3times,
stopsfor3s
Roomsensorunplugged
ordamaged.
1. CheckifTrplugisconnectedornot.
2. Checkifsensor’sresistanceiscorrect
ornot.
Indoorcoilsensor1failure
GreenLEDblinks4times,
stopsfor3s
Ti1sensorunpluggedor
damaged.
1. CheckifTi1plugisconnectedornot.
2. Checkifsensor’sresistanceiscorrect
ornot.
Indoorcoillowtemperature
protection
GreenLEDblinks5times,
stopsfor3s
Watertemperatureis
lowerthan3ºC.
Checkthewatertemperature.
Indoorcoiloverheat
protection
GreenLEDblinks6times,
stopsfor3s
Watertemperatureis
higherthan70ºC.
Checkthewatertemperature
ECmotorfailure
GreenLEDblinks9times,
stopsfor3s
NoECmotorfeedback
1. CheckDIPBSW5andSW6setting.
2. ChecktheECmotor.