EasyManuals Logo
Home>Danfoss>DC Drives>Metasys N2

Danfoss Metasys N2 Operating Instructions

Danfoss Metasys N2
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
15-20 Historic Log: Event to 15-22 Historic Log: Time
15-30 Alarm Log: Error Code to 15-32 Alarm Log: Time
NOTICE
Parameters selected in 0-25 My Personal Menu stay
present with default factory setting.
Manual initialisation
NOTICE
When carrying out manual initialisation, serial communi-
cation, RFI filter settings and fault log settings are reset.
Removes parameters selected in 0-25 My Personal Menu.
1. Disconnect from mains and wait until the display
turns off.
2. Press
2a [Status] - [Main Menu] - [OK] at the
same time while power up for Graphical
LCP (GLCP).
2b [Menu] while power up for LCP 101,
Numerical Display.
3. Release the keys after 5 s.
4. The frequency converter is now programmed
according to default settings.
This parameter initialises all except:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
How to Operate the Frequenc... VLT HVAC Drive FC 102 Operating Instructions
MG11F402 - Rev. 2013-12-16 79
5 5

Table of Contents

Other manuals for Danfoss Metasys N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Metasys N2 and is the answer not in the manual?

Danfoss Metasys N2 Specifications

General IconGeneral
BrandDanfoss
ModelMetasys N2
CategoryDC Drives
LanguageEnglish

Related product manuals