Page 35 of 108
M-AP-001-EN Rev. N
Table 5-5 - Suction Pressure
Alarm and Trip Settings
The Suction Pressure alarm and trip limits are displayed in the Table 5-5.5.4 Suction Pressure
Limits
Alarm Trip
Model kPa(g) PSIG kPa(g) PSIG
TG230ST 99 14 79 11
TG230MT 40 6 29 4
TG310 99 14 79 11
TG390 99 14 96 14
TG520 99 14 96 14
TT300ST 177 26 152 22
TT300MT 91 13 76 11
TT350 177 26 152 22
TT400 177 26 166 24
TT700 177 26 166 24
NOTE
Pressure ratio is the ratio of absolute discharge to absolute suction pressure. It can be calculated as follows:
• (DP + 101) / (SP + 101) (kPa) OR
• (DP + 14.7) / (SP + 14.7) (psi)
• TT and TG Series Turbocor Compressors were designed for use in stationary
building applications.
• An OEMs use of Turbocor Compressors in applications other than stationary
building applications (e.g. Marine Applications) is considered a non-standard
application and is not eligible for warranty under DTCs standard warranty Terms
and Conditions.
It is the responsibility of the OEM to ensure that proper safety protocols are in place and that
the chiller system has been designed in a manner that is compliant with all local codes and
regulatory requirements governing the use of refrigerants, pressure, vessels, and electrical
power. OEMs must also ensure compliance with the requirements stated in the refrigerant
manufacturer’s Material Safety Data Sheet (MSDS) and that other system components are
compatible with the refrigerant, giving special attention to elastomers and seals.
5.5 Codes and Standards
Compliance
General Specications