Page 98 of 108
M-AP-001-EN Rev. N
M-AP-001-EN Rev. N
Installation
20.6.2 Circuit Grounding Improper grounding or voltage in circuits connected to the compressor I/O board can lead
to component failures. In particular, the interlock and analog output circuits are sensitive to
improperly connected external circuits (see Figure 20-7).
Prior to connecting the control wiring to the compressor I/O board, check for improper
grounding. Improper grounding can be identied by measuring the voltage between the
customer’s negative terminals and the ground (J1 COM or Modbus shield) terminal on the
compressor I/O board (see Figure 20-7). If the measured voltage is not zero, determine
the source of the voltage. The most likely cause of voltage is insucient insulation of the
external circuit. In case of uncertainty of the grounding, connect the negative terminals of
the external circuit to a ground and then connect the external ground to the ground on the
compressor I/O board.
Figure 20-7 - Interlock and
Motor Speed Connections