23-04 Occurrence
Array [10]
Option: Function:
Select which day(s) the Timed Action applies to. Specify working/non-working days in par.
0-81 Working
Days
, par. 0-82 Additional
Working Days
and par. 0-83 Additional
Non-Working
Days
.
[0] * All days
[1] Working days
[2] Non-working days
[3] Monday
[4] Tuesday
[5] Wednesday
[6] Thursday
[7] Friday
[8] Saturday
[9] Sunday
8.2.12. Water Application Functions, 29-**
The group contains parameters used for monitoring water / wastewater applications.
29-00 Pipe Fill Enable
Option: Function:
[0] * Disabled Select Enabled to fill pipes at a user specified rate.
[1] Enabled Select Enabled to fill pipes with a user specified rate.
29-01 Pipe Fill Speed [RPM]
Range: Function:
Speed Low
Limit*
[Speed Low Limit - Speed High Lim-
it]
Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPM
depending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).
29-02 Pipe Fill Speed [Hz]
Range: Function:
Motor
Speed Low
Limit*
[Speed Low Limit - Speed High Lim-
it]
Set the filling speed for filling horizontal pipe systems. The speed can be selected in Hz or RPM
depending on the choices made in par. 4-11 / par. 4-13 (RPM) or in par. 4-12 / par. 4-14 (Hz).
29-03 Pipe Fill Time
Range: Function:
0 s* [0 - 3600 s] Set the specified time for pipe filling of horizontal pipe systems.
29-04 Pipe Fill Rate
Range: Function:
0.001 units/
s*
[0.001 – 999999.999 units/s] Specifies the filling rate in units/second using the PI controller. Filling rate units are feedback units/
second. This function is used for filling-up vertical pipe systems but will be active when the filling-
time has expired, no matter what , until the pipe fill-set-point set in par. 29-05 is reached.
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
107
8