Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
26-0* Analog I/O Mode
26-00 Terminal X42/1 Mode [1] Voltage All set-ups TRUE - Uint8
26-01 Terminal X42/3 Mode [1] Voltage All set-ups TRUE - Uint8
26-02 Terminal X42/5 Mode [1] Voltage All set-ups TRUE - Uint8
26-1* Analog Input X42/1
26-10 Terminal X42/1 Low Voltage 0.07 V All set-ups TRUE -2 Int16
26-11 Terminal X42/1 High Voltage 10.00 V All set-ups TRUE -2 Int16
26-14 Term. X42/1 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
26-15 Term. X42/1 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
26-16 Term. X42/1 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
26-17 Term. X42/1 Live Zero [1] Enabled All set-ups TRUE - Uint8
26-2* Analog Input X42/3
26-20 Terminal X42/3 Low Voltage 0.07 V All set-ups TRUE -2 Int16
26-21 Terminal X42/3 High Voltage 10.00 V All set-ups TRUE -2 Int16
26-24 Term. X42/3 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
26-25 Term. X42/3 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
26-26 Term. X42/3 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
26-27 Term. X42/3 Live Zero [1] Enabled All set-ups TRUE - Uint8
26-3* Analog Input X42/5
26-30 Terminal X42/5 Low Voltage 0.07 V All set-ups TRUE -2 Int16
26-31 Terminal X42/5 High Voltage 10.00 V All set-ups TRUE -2 Int16
26-34 Term. X42/5 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
26-35 Term. X42/5 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
26-36 Term. X42/5 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
26-37 Term. X42/5 Live Zero [1] Enabled All set-ups TRUE - Uint8
26-4* Analog Out X42/7
26-40 Terminal X42/7 Output [0] No operation All set-ups TRUE - Uint8
26-41 Terminal X42/7 Min. Scale 0.00 % All set-ups TRUE -2 Int16
26-42 Terminal X42/7 Max. Scale 100.00 % All set-ups TRUE -2 Int16
26-43 Terminal X42/7 Bus Control 0.00 % All set-ups TRUE -2 N2
26-44 Terminal X42/7 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
26-5* Analog Out X42/9
26-50 Terminal X42/9 Output [0] No operation All set-ups TRUE - Uint8
26-51 Terminal X42/9 Min. Scale 0.00 % All set-ups TRUE -2 Int16
26-52 Terminal X42/9 Max. Scale 100.00 % All set-ups TRUE -2 Int16
26-53 Terminal X42/9 Bus Control 0.00 % All set-ups TRUE -2 N2
26-54 Terminal X42/9 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
26-6* Analog Out X42/11
26-60 Terminal X42/11 Output [0] No operation All set-ups TRUE - Uint8
26-61 Terminal X42/11 Min. Scale 0.00 % All set-ups TRUE -2 Int16
26-62 Terminal X42/11 Max. Scale 100.00 % All set-ups TRUE -2 Int16
26-63 Terminal X42/11 Bus Control 0.00 % All set-ups TRUE -2 N2
26-64 Terminal X42/11 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
8.3.22. Analog I/O Option MCB 109 26-**
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
135
8

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals