22-35 Low Speed Power [HP]
Range: Function:
0 hp* [0.00 - 0.00 hp] To be used if par. 0-03 Regional
Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-36 High Speed [RPM]
Range: Function:
0 RPM* [0 - par. 4-13 RPM] To be used if par. 0-02 Motor
Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-37 High Speed [Hz]
Range: Function:
0.0 Hz* [0.0 - par. 4-14 Hz] To be used if par. 0-02 Motor
Speed Unit
has been set for Hz (parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
22-38 High Speed Power [kW]
Range: Function:
0 kW* [0.00 - 0.00 kW] To be used if par. 0-03 Regional
Settings
has been set for International (parameter not visible if
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-39 High Speed Power [HP]
Range: Function:
0 hp* [0.00 - 0.00 hp] To be used if par. 0-03 Regional
Settings
has been set for North America (parameter not visible if
International selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
22-40 Minimum Run Time
Range: Function:
10 s* [0 - 600 s] Set the desired minimum running time for the motor after a Start command (digital input or Bus)
before entering Sleep Mode.
22-41 Minimum Sleep Time
Range: Function:
10 s* [0 - 600 s] Set the desired minimum time for staying in Sleep Mode. This will override any wake up conditions.
22-42 Wake-up Speed [RPM]
Range: Function:
0 RPM* [par. 4-11 - par. 4-13 RPM] To be used if par. 0-02 Motor
Speed Unit
has been set for RPM (parameter not visible if Hz selected).
Only to be used if par. 1-00
Configuration Mode
is set for Open Loop and speed reference is applied
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M5.02 - VLT
®
is a registered Danfoss trademark
99
8

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals