22-34 Low Speed Power [kW]
Range: Function:
0
*
[0.0 - par. 22-38] To be used if par. 0-03,
Regional Settings
, has been set for In-
ternational (parameter not visible if North America selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow
Detection.
22-35 Low Speed Power [Hp]
Range: Function:
0
*
[0.0 - Par. 22-39] To be used if par. 0-03,
Regional Settings
, has been set for
North America (parameter not visible if International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow
Detection.
22-36 High Speed [RPM]
Range: Function:
0 RPM
*
[0.0 - par. 4-13 (Mo-
tor High Speed Limit)]
To be used if par. 0-02,
Motor Speed Unit
, has been set for RPM
(parameter not visible if Hz selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow
Detection.
22-37 High Speed [Hz]
Range: Function:
0 Hz
*
[] To be used if par. 0-02,
Motor Speed Unit
has been set for Hz
(parameter not visible if RPM selected).
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow
Detection.
22-38 High Speed Power [kW]
Range: Function:
0
*
[0.0 - Max Motor Out-
put]
To be used if par. 0-03,
Regional Settings
, has been set for In-
ternational (parameter not visible if North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow
Detection.
22-39 High Speed Power [Hp]
Range: Function:
0
*
[0.0 - Max Motor Out-
put]
To be used if par. 0-03,
Regional Settings
, has been set for North
America (parameter not visible if International selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow
Detection.