2.9. Main Menu - Communications and Options - Group
8
2.9.1. 8-** Comm. and Options
Parameter group for configuring communications and options.
2.9.2. 8-0* General Settings
General settings for communications and options.
8-01 Control Site
Option: Function:
[0]
*
Digital and ctrl. word Control by using both digital input and control word.
[1] Digital only Control by using digital inputs only.
[2] Control word only Control by using control word only.
The setting in this parameter overrides the settings in par. 8-50
to 8-56.
8-02 Control Word Source
Option: Function:
Select the source of the control word: one of two serial interfa-
ces or four installed options. During initial power-up, the fre-
quency converter automatically sets this parameter to
Option
A
[3] if it detects a valid fieldbus option installed in slot A. If the
option is removed, the frequency converter detects a change in
the configuration, sets par. 8-02 back to default setting
FC
Port
, and the frequency converter then trips. If an option is in-
stalled after initial power-up, the setting of par. 8-02 will not
change but the frequency converter will trip and display: Alarm
67
Option Changed
.
This parameter cannot be adjusted while the motor is running.
[0] None
[1] FC Port
[2] FC USB
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
107