EasyManua.ls Logo

Danfoss vlt aqua - Analog In;Out

Danfoss vlt aqua
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-95 Pulse Out #29 Bus Control
Range: Function:
0 %
*
[1 - 100 %] Contains the frequency to apply to the digital output terminal
29, when it is configured as [Bus Controlled].
5-96 Pulse Out #29 Timeout Preset
Range: Function:
0 %
*
[1 - 100 %] Contains the frequency to apply to the digital output terminal
29, when it is configured as [Bus Controlled Timeout] and time-
out is detected
5-97 Pulse Out #X30/6 Bus Control
Range: Function:
0 %
*
[1 - 100 %] Contains the frequency to apply to the digital output terminal
27, when it is configured as [Bus Controlled.
5-98 Pulse Out #X30/6 Timeout Preset
Range: Function:
0 %
*
[1 - 100 %] Contains the frequency to apply to the digital output terminal 6,
when it is configured as [Bus Controlled Timeout] and timeout
is detected.
2.8. Main Menu - Analog In/Out - Group 6
2.8.1. 6-** Analog In/Out
Parameter group for configuration of the analog input and output.
2.8.2. 6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The frequency converter is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs
can freely be allocated to either voltage (0 V - 10 V) or current input (0/4 - 20 mA)
NB!
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range: Function:
10s
*
[1 - 99 s] Enter the Live Zero Time-out time period. Live Zero Time-out
Time is active for analog inputs, i.e. terminal 53 or terminal 54,
2. Parameter Description VLT
®
AQUA Drive Programming Guide
96
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Related product manuals