2.9.8. 8-9* Bus Jog
Parameters for configuring the Bus Jog.
8-90 Bus Jog 1 Speed
Range: Function:
100
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
8-94 Bus Feedback 1
Range: Function:
0
*
[-200 - 200] Write a feedback to this parameter via the serial communication
port or fieldbus option. This parameter must be selected in par.
20-00, 20-03 or 20-06 as a feedback source.
8-95 Bus Feedback 2
Range: Function:
0
*
[-200 - 200] See par. 8-94
Bus Feedback 1
for further details.
8-96 Bus Feedback 3
Range: Function:
0
*
[-200 - 200] See par. 8-94
Bus Feedback 1
for further details.
2.10. Main Menu - Profibus - Group 9
2.10.1. 9-** Profibus
Parameter group for all Profibus-specific parameters. Only available if Profibus option is mounted
9-15 PCD Write Configuration
Array [10]
Select the parameters to be assigned to PCD 3 to 10 of the tele-
grams. The number of available PCDs depends on the telegram
type. The values in PCD 3 to 10 will then be written to the se-
lected parameters as data values. Alternatively, specify a stand-
ard Profibus telegram in par. 9-22.
None
VLT
®
AQUA Drive Programming Guide 2. Parameter Description
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
115
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals