Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
8-0* General Settings
8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE - Uint8
8-02 Control Source [0] None All set-ups TRUE - Uint8
8-03 Control Timeout Time SR 1 set-up TRUE -1 Uint32
8-04 Control Timeout Function [0] Off 1 set-up TRUE - Uint8
8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint8
8-06 Reset Control Timeout [0] Do not reset All set-ups TRUE - Uint8
8-07
Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint8
8-1* Control Settings
8-10 Control Profile [0] FC profile All set-ups TRUE - Uint8
8-13 Configurable Status Word STW [1] Profile Default All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE - Uint8
8-31 Address 1 N/A 1 set-up TRUE 0 Uint8
8-32 Baud Rate null 1 set-up TRUE - Uint8
8-33 Parity / Stop Bits null 1 set-up TRUE - Uint8
8-35 Minimum Response Delay 10 ms 1 set-up TRUE -3 Uint16
8-36 Max Response Delay SR 1 set-up TRUE -3 Uint16
8-37 Max Inter-Char Delay SR 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram Selection [1] Standard telegram 1 2 set-ups TRUE - Uint8
8-5* Digital/Bus
8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8
8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8
8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8
8-54 Reversing Select [0] Digital input All set-ups TRUE - Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8
8-56
Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8
8-7* BACnet
8-70 BACnet Device Instance 1 N/A 1 set-up TRUE 0 Uint32
8-72 MS/TP Max Masters 127 N/A 1 set-up TRUE 0 Uint8
8-73 MS/TP Max Info Frames 1 N/A 1 set-up TRUE 0 Uint16
8-74 "I-Am" Service [0] Send at power-up 1 set-up TRUE - Uint8
8-75
Initialisation Password 0 N/A 1 set-up TRUE 0 VisStr[20]
8-8* FC Port Diagnostics
8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave Message Count 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint32
8-9* Bus Jog / Feedback
8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE 67 Uint16
8-91 Bus Jog 2 Speed 200 RPM All set-ups TRUE 67 Uint16
8-94 Bus Feedback 1 0 N/A 1 set-up TRUE 0 N2
8-95 Bus Feedback 2 0 N/A 1 set-up TRUE 0 N2
8-96 Bus Feedback 3 0 N/A 1 set-up TRUE 0 N2
3.1.9. 8-** Comm. and Options
3. Parameter Lists VLT
®
AQUA Drive Programming Guide
268
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark