The relation will depend on the type of unit selected in par.0-30, Custom Readout Unit:
Unit Type
Speed Relation
Dimensionless Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure Quadratic
Power Cubic
0-30 Custom Readout Unit
Option: Function:
Program a value to be shown in the display of the LCP. The value
has a linear, squared or cubed relation to speed. This relation
depends on the unit selected (see table above). The actual cal-
culated value can be read in
Custom Readout
, par. 16-09, and/
or shown in the display be selecting Custom Readout [16-09] in
par. 0-20 – 0-24, Display Line X.X Small (large).
Dimensionless:
[0] None
[1]
*
%
[5] PPM
Speed:
[10] 1/min
[11] RPM
[12] Pulse/s
Flow, volume:
[20] l/s
[21] l/min
[22] l/h
2. Parameter Description VLT
®
AQUA Drive Programming Guide
36
MG.20.O2.02 - VLT
®
is a registered Danfoss trademark
2

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals