5.2.9 Ordering Numbers: dU/dt Filters, 200-690 V AC
Frequency converter ratings Filter current rating Ordering no.
200-240 V 380-440 V 441-500 V 525-550 V 551-690 V
380 V@60
Hz
200-400/44
0 V@50 Hz
460/480
V@60 Hz
500/525
V@5 0Hz
575/600
V@60 Hz
690
V@50 Hz
IP00 IP20* IP54
[kW] [A] [kW] [A] [kW] [A] [kW] [A] [kW] [A] [A] [A] [A] [A]
3 12.5 5.5 13 5.5 11 5.5 9.5 1.1 1.6
17 15 13 13 N/A
130B
7367*
N/A
3.7 16 7.5 16 7.5 14.5 7.5 11.5 1.5 2.2
- - - - - - - -
2.2 3.2
3 4.5
4 5.5
5.5 7.5
7.5 10
5.5 24.2 11 24 11 21 7,5 14 11 13
44 40 32 27
130B
2835
130B
2836
130B
2837
7.5 30.8 15 32 15 27 11 19 15 18
- - 18.5 37.5 18.5 34 15 23 18.5 22
- - 22 44 22 40 18,5 28 22 27
11 46.2 30 61 30 52 30 43 30 34
90 80 58 54
130B
2838
130B
2839
130B
2840
15 59.4 37 73 37 65 37 54 37 41
18.5 74.8 45 90 55 80 45 65 45 52
22 88 - - - - - - - -
- -
55 106 75 105 55 87
55 62
106 105 94 86
103B
2841
103B
2842
103B
2843
- - 75 83
30 115 75 147 90 130 75 113 90 108
177 160 131 108
130B
2844
130B
2845
130B
2846
37 143 90 177 - - 90 137 - -
45 170 - - - - - - - -
Table 5.24 dU/dt Filters 3x200-690 V IP00/IP20/IP54
Frequency converter power rating: power ratings correspond to both HO and NO ratings. Changing the FC 300 to NO will change the operating
conditions.
* Dedicated A3 enclosure types supporting foot print mounting and book style mounting. Fixed screened cable connection to frequency converter.
Parameter Setting
14-01 Switching Frequency Higher operating switching frequency than specified by the individual filter is not recommended.
14-55 Output Filter Select no filter.
14-56 Capacitance Output Filter* Set according the individual filter. Listed at filter product label and in output filter manual.
14-57 Inductance Output Filter* Set according the individual filter. Listed at filter product label and in output filter manual.
Table 5.25 Parameter Settings for dU/dt Filter Operation
* For Flux control principle.
How to Order
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW