9 Options and Accessories
Danfoss offers a wide range of options and accessories.
9.1.1 Mounting of Option Modules in
Slot A
Slot A position is dedicated to Fieldbus options. For further
information, see separate operating instructions.
9.1.2 Mounting of Option Modules in
Slot B
The power to the frequency converter must be discon-
nected.
It is strongly recommended to make sure the parameter
data is saved (i.e. by MCT 10 software) before option
modules are inserted/removed from the drive.
•
Remove the LCP (Local Control Panel), the
terminal cover, and the LCP frame from the
frequency converter.
•
Fit the MCB10xy option card into slot B.
•
Connect the control cables and relieve the cable
by the enclosed cable strips.
* Remove the knock out in the extended LCP
frame, so that the option will fit under the
extended LCP frame.
•
Fit the extended LCP frame and terminal cover.
•
Fit the LCP or blind cover in the extended LCP
frame.
•
Connect power to the frequency converter.
•
Set up the input/output functions in the
corresponding parameters, as mentioned in .
LCP
Frame
A
B
D
130BA707.10
XXXN1100
3x380-480V 50/60Hz 14.9A
OUT: 3x0-Uin 0-1000Hz 16.0A 11.1 kVA
CHASIS/IP20 Tamb Max 45C/113F
MADE IN DENMARK
CAUTION:
SEE MANUAL / RCD and high leakage current
VOIR MANUAL / Fransk tekst
WARNING:
Stored charge / “Fransk tekst” (4 min.)
LISTED 76x1 134261
INDUSTRIAL CONTROL EQUIPMENT
SEE MANUAL FOR PREFUSE TUPE IN UL
APPLICATIONS
Illustration 9.1 Frame Sizes A2, A3 and B3
LCP
Cradle
DC-
DC+
130BA708.10
13
12
18
19
27
28
32
38
2
42
39
53
50
5
61
6
Remove jumper to activate Safe Stop
9Ø
9Ø
Illustration 9.2 Frame Sizes A5, B1, B2, B4, C1, C2, C3 and C4
9.1.3 Mounting of Options in Slot C
The power to the frequency converter must be discon-
nected.
It is strongly recommended to make sure the parameter
data is saved (i.e. by MCT 10 software ) before option
modules are inserted/removed from the drive.
When installing a C option, a mounting kit is required.
Please refer to 5 How to Order for a list of ordering
numbers. The installation is illustrated using MCB 112 as
an example. For more information on installation of MCO
305, see 9.2 MCO 305 Programmable Motion Controller and
separate operating instructions.