8 Application Examples
NOTE
When the optional safe stop feature is used, a jumper wire
may be required between terminal 12 (or 13) and terminal
37 for the frequency converter to operate when using
factory default programming values.
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings)
•
Parameters associated with the terminals and
their settings are shown next to the drawings
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
CAUTION
Thermistors must use reinforced or double insulation to
meet PELV insulation requirements.
Parameters
Function Setting
1-29 Automatic
Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
5-12 Terminal 27
Digital Input
[2]* Coast
inverse
*=Default Value
Notes/comments: Parameter
group 1-2* Motor Data must be
set according to motor
Table 8.1 AMA with T27 Connected
Parameters
Function Setting
1-29 Automatic
Motor
Adaptation
(AMA)
[1] Enable
complete
AMA
5-12 Terminal 27
Digital Input
[0] No
operation
*=Default Value
Notes/comments: Parameter
group 1-2* Motor Data must be
set according to motor
Table 8.2 AMA without T27 Connected
Parameters
Function Setting
6-10 Terminal 53
Low Voltage 0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0 RPM
6-15 Terminal 53
High Ref./Feedb.
Value
1500 RPM
*=Default Value
Notes/comments:
Table 8.3 Analog Speed Reference (Voltage)
Application Examples
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
MG33BE02 - VLT
®
is a registered Danfoss trademark 149
8 8