Hole Number
and
recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 1 34.7 M32
2) Motor 1 34.7 M32
3) Brake/Load
Sharing
1 34.7 M32
4) Control
Cable
1/2 22.5 M20
5) Control
Cable
1/2 22.5 M20
6) Control
Cable
1/2 22.5 M20
Table 7.15 Legend to Illustration 7.34
1)
Tolerance
±
0.2 mm
[5]
[3]
[2]
[4]
[1]
130BB661.10
Illustration 7.35 C1 - IP21
Hole Number
and
recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 2 63.3 M63
2) Motor 2 63.3 M63
3) Brake/Load
Sharing
1 1/2 50.2 M50
4) Control
Cable
3/4 28.4 M25
5) Control
Cable
1/2 22.5 M20
Table 7.16 Legend to Illustration 7.35
1)
Tolerance
±
0.2 mm
[5]
[3]
[2]
[6]
[4]
[1]
130BB662.10
Illustration 7.36 C2 - IP21
Hole Number
and
recommended
use
Dimensions
1)
Nearest metric
UL [in] [mm]
1) Mains 2 63.3 M63
2) Motor 2 63.3 M63
3) Brake/Load
Sharing
1 1/2 50.2 M50
4) Control
Cable
3/4 28.4 M25
5) Control
Cable
1/2 22.5 M20
6) Control
Cable
1/2 22.5 M20
Table 7.17 Legend to Illustration 7.36
1)
Tolerance
±
0.2 mm
7.1.4
Relay Connection
To set relay output, see parameter group 5-4* Relays.
No.
01 - 02 make (normally open)
01 - 03 break (normally closed)
04 - 05 make (normally open)
04 - 06 break (normally closed)
Table 7.18 Description of Relays
130BA029.12
Relay2
Relay1
35 36
Illustration 7.37 Terminals for relay connection
(Frame sizes A1, A2 and A3).
Electrical Installation
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
MG33BE02 - VLT
®
is a registered Danfoss trademark 121