9.6 Relay Option MCB 105
The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data
Max terminal load (AC-1)
1)
(Resistive load) 240 V AC 2 A
Max terminal load (AC-15 )
1)
(Inductive load @ cosφ 0.4) 240 V AC 0.2 A
Max terminal load (DC-1)
1)
(Resistive load) 24 V DC 1 A
Max terminal load (DC-13)
1)
(Inductive load) 24 V DC 0.1 A
Min terminal load (DC) 5 V 10 mA
Max switching rate at rated load/min load 6 min
-1
/20 s
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately the kit
includes:
Relay Module MCB 105
Enlarged LCP fixture and enlarged terminal cover
Label for covering access to switches S201, S202
and S801
Cable strips for fastening cables to relay module
The relay option does not support FC 302 frequency
converters manufactured before week 50/2004.
Min. software version: 2.03 (15-43 Software Version).
130BA709.10
1
LABEL
DISMOUNT RELAY CARD TO ACCESS RS485
TERMINATION (S801) OR CURRENT/VOLTAGE
SWITCHES (S201, S202)
Remove jumper to activate Safe Stop
12
13
18
19
27
29
33
32
20
39
42
50
53
54
61 68
CAUTION:
SEE MANUAL / RCD and high leakage current
VOIR MANUAL / Fransk tekst
WARNING:
Stored charge / “Fransk tekst” (4 min.)
LISTED 76x1 134261
INDUSTRIAL CONTROL EQUIPMENT
SEE MANUAL FOR PREFUSE TUPE IN UL
APPLICATIONS
T/C : CIAXXXPT5B20BR1DBF00A00
P/N : XXXN1100 S/N: 012815G432
IN: 3x380-480V 50/60Hz 14.9A
OUT: 3x0-Uin 0-1000Hz 16.0A 11.1 kVA
CHASIS/IP20 Tamb Max 45C/113F
MADE IN DENMARK
Ø6
Illustration 9.17 A2-A3-B3
1 IMPORTANT ! The label MUST be placed on the LCP frame as
shown (UL approved).
Table 9.12 Legend to Illustration 9.17
130BA710.10
1
DISMOUNT RELAY CARD TO ACCESS RS485
TERMINATION (S801) OR CURRENT/VOLTAGE
SWITCHES (S201, S202)
LABEL
Remove jumper to activate Safe Stop
13
12
18
19
27
32
38
2
28
42
39
53
50
5
61
6
DC-
DC+
Illustration 9.18 A5-B1-B2-B4-C1-C2-C3-C4
1 IMPORTANT ! The label MUST be placed on the LCP frame as
shown (UL approved).
Table 9.13 Legend to Illustration 9.18
WARNING
Warning Dual supply
How to add the MCB 105 option:
The power to the frequency converter must be
disconnected.
The power to the live part connections on relay
terminals must be disconnected.
Remove the LCP, the terminal cover and the LCP
fixture from the frequency converter.
Fit the MCB 105 option in slot B.
Connect the control cables and fasten the cables
with the enclosed cable strips.
Make sure the length of the stripped wire is
correct (see the following drawing).
Do not mix live parts (high voltage) with control
signals (PELV).
Fit the enlarged LCP fixture and enlarged
terminal cover.
Replace the LCP.
Connect power to the frequency converter.
Options and Accessories
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
MG33BE02 - VLT
®
is a registered Danfoss trademark 167
9 9
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-21462-Danfoss-131B8966-VLT-Automation-VT-Drive-VFD-FC301-230V-5-HP.aspx

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Related product manuals