9.6 Relay Option MCB 105
The MCB 105 option includes 3 pieces of SPDT contacts and must be fitted into option slot B.
Electrical Data
Max terminal load (AC-1)
1)
(Resistive load) 240 V AC 2 A
Max terminal load (AC-15 )
1)
(Inductive load @ cosφ 0.4) 240 V AC 0.2 A
Max terminal load (DC-1)
1)
(Resistive load) 24 V DC 1 A
Max terminal load (DC-13)
1)
(Inductive load) 24 V DC 0.1 A
Min terminal load (DC) 5 V 10 mA
Max switching rate at rated load/min load 6 min
-1
/20 s
-1
1) IEC 947 part 4 and 5
When the relay option kit is ordered separately the kit
includes:
•
Relay Module MCB 105
•
Enlarged LCP fixture and enlarged terminal cover
•
Label for covering access to switches S201, S202
and S801
•
Cable strips for fastening cables to relay module
The relay option does not support FC 302 frequency
converters manufactured before week 50/2004.
Min. software version: 2.03 (15-43 Software Version).
130BA709.10
1
LABEL
DISMOUNT RELAY CARD TO ACCESS RS485
TERMINATION (S801) OR CURRENT/VOLTAGE
SWITCHES (S201, S202)
Remove jumper to activate Safe Stop
12
13
18
19
27
29
33
32
20
39
42
50
53
54
61 68
CAUTION:
SEE MANUAL / RCD and high leakage current
VOIR MANUAL / Fransk tekst
WARNING:
Stored charge / “Fransk tekst” (4 min.)
LISTED 76x1 134261
INDUSTRIAL CONTROL EQUIPMENT
SEE MANUAL FOR PREFUSE TUPE IN UL
APPLICATIONS
T/C : CIAXXXPT5B20BR1DBF00A00
P/N : XXXN1100 S/N: 012815G432
IN: 3x380-480V 50/60Hz 14.9A
OUT: 3x0-Uin 0-1000Hz 16.0A 11.1 kVA
CHASIS/IP20 Tamb Max 45C/113F
MADE IN DENMARK
9Ø
9Ø
Ø6
Illustration 9.17 A2-A3-B3
1 IMPORTANT ! The label MUST be placed on the LCP frame as
shown (UL approved).
Table 9.12 Legend to Illustration 9.17
130BA710.10
1
DISMOUNT RELAY CARD TO ACCESS RS485
TERMINATION (S801) OR CURRENT/VOLTAGE
SWITCHES (S201, S202)
LABEL
Remove jumper to activate Safe Stop
13
12
18
19
27
32
38
2
28
42
39
53
50
5
61
6
9Ø
9Ø
DC-
DC+
Illustration 9.18 A5-B1-B2-B4-C1-C2-C3-C4
1 IMPORTANT ! The label MUST be placed on the LCP frame as
shown (UL approved).
Table 9.13 Legend to Illustration 9.18
WARNING
Warning Dual supply
How to add the MCB 105 option:
•
The power to the frequency converter must be
disconnected.
•
The power to the live part connections on relay
terminals must be disconnected.
•
Remove the LCP, the terminal cover and the LCP
fixture from the frequency converter.
•
Fit the MCB 105 option in slot B.
•
Connect the control cables and fasten the cables
with the enclosed cable strips.
•
Make sure the length of the stripped wire is
correct (see the following drawing).
•
Do not mix live parts (high voltage) with control
signals (PELV).
•
Fit the enlarged LCP fixture and enlarged
terminal cover.
•
Replace the LCP.
•
Connect power to the frequency converter.
Options and Accessories
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
MG33BE02 - VLT
®
is a registered Danfoss trademark 167
9 9