1-00 Configuration Mode determines what kind of
application control principle (i.e. Speed, Torque or Process
Control) is used when the remote reference is active.
1-05 Local Mode Configuration determines the kind of
application control principle that is used when the local
reference is active. One of them is always active, but both
can not be active at the same time.
3.3 Reference Handling
Local Reference
The local reference is active when the frequency converter
is operated with [Hand On] active. Adjust the reference by
[
]/[
] and []/[] navigation keys respectively.
Remote Reference
The reference handling system for calculating the Remote
reference is shown in Illustration 3.9.
Introduction
VLT
®
AutomationDrive FC 300 Design Guide, 0.25-75 kW
22 MG33BE02 - VLT
®
is a registered Danfoss trademark
3
3