Illustration 10.10 Text via PWE Block
10.6.11 Supported Data Types
Unsigned means that there is no operational sign in the
telegram.
Data types Description
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9 Text string
10 Byte string
13 Time difference
33 Reserved
35 Bit sequence
Table 10.7 Supported Data Types
10.6.12
Conversion
The various attributes of each parameter are displayed in
Factory Setting. Parameter values are transferred as whole
numbers only. Conversion factors are therefore used to
transfer decimals.
4-12 Motor Speed Low Limit [Hz] has a conversion factor of
0.1. To preset the minimum frequency to 10 Hz, transfer
the value 100. A conversion factor of 0.1 means that the
value transferred is multiplied by 0.1. The value 100 is
therefore read as 10.0.
Examples:
0s ⇒ conversion index 0
0.00s ⇒ conversion index -2
0ms ⇒ conversion index -3
0.00ms ⇒ conversion index -5
Conversion index
Conversion factor
100
75
74
67
6 1000000
5 100000
4 10000
3 1000
2 100
1 10
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
-6 0.000001
-7 0.0000001
Table 10.8 Conversion Table
10.6.13
Process Words (PCD)
The block of process words is divided into two blocks of
16 bits, which always occur in the defined sequence.
PCD 1
PCD 2
Control telegram (master⇒ slave Control
word)
Reference-value
Control telegram (slave⇒ master) Status word
Present output
frequency
Table 10.9 Process Words (PCD)
10.7
Examples
10.7.1 Writing a Parameter Value
Change 4-14 Motor Speed High Limit [Hz] to 100 Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in 4-14 Motor Speed
High Limit [Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to
100 Hz, see 10.6.12 Conversion.